1: The synopsis of Solar / wind power inverter
Solar / wind power inverteris pure sine wave intelligent inverter; Through the inverter power supply, 48V DC battery can be converted into 110V AC Alternating Current, Used to power the load; Solar power system consists of solar panel, Solar charge controller, inverter, battery and other components; Can be divided into several types: Only the converter, Give priority to the use of solar energy, Give priority to the use of AC;
Solar power generation system for DC48V;
DC input can also be customized DC12V/DC24V/DC36V/DC48V; AC input can choose AC100V, AC120V, AC220V, AC230V, AC240V etc; The frequency of 50/60Hz automatic detection.
The core advantage:
CPU intelligent management, Latest American technical inverter, Adopted best electronic components, stable quality, long-life, The high conversion efficiency( 90%~99%), Low power consumption, 1W~6W under sleep state.
2: The use mode of Solar / wind power inverter
<1>Only the converter
DC power generated by solar panels, Solar controller provides stable electrical energy, Solar controller usually charge the battery, When using the electrical energy, through the inverter, the DC can be converted into AC electrical energy, Sine wave AC power supply for users.
3. The city electricity and solar energy use the interactive type
1: Give priority to the use of AC:
DC power generated by solar panels, Solar controller provides stable electrical energy, Solar controller usually charge the battery, When the normal electricity, Used AC power. When the AC power is off, through the inverter, the DC can be converted into AC electrical energy, Sine wave AC power supply for users. (Electric charging function can be cancelled on the panel, Please switch to 0-9 position 0)
2: Give priority to the use of solar energy:
DC power generated by solar panels, Solar controller provides stable electrical energy, Solar controller usually charge the battery, When using the electric energy, Through the inverter, the DC can be converted into AC electrical energy, Sine wave AC power supply for users. When the battery voltage is too low, it is under voltage protection, automatically switched to the AC power supply. (Electric charging function can be cancelled on the panel, Please switch to 0-9 position 0)
3: The product features of Solar / wind power inverter
Pure sine wave output;
Built-in transfer switch automatically transfers between inverter power and incoming AC power.
CPU management, intelligent control, module design.
LED/LCD display function;
High conversion efficiency (between 90%-98%) low consumption.
Can match with all kinds of batteris, such as sealed lead acid battery, open lead acid battery, gel battery and kinds of lithium batteries.
Three-step intelligent charging mode available. It charges all kinds of batteries intelligently. And the maximum charging current is adjustable.
It also can be used as a charger.
This series inverter is also called dynamic inverter according to the advantage of strong overload capacity. For example, 1KW model can drive 1P air conditioning. 2KW can drive 2P air conditioning, 3KW can drive3P air conditioning etc.
With adopting latest American low frequency circuit design, and new electronic materials, the whole system is more stable, low malfunction rate, long-life. It is no problem to use for more than 8 years under the normal use.
2-year warranty plus life-time service.
Protection: High voltage protection
Low-voltage protection
Over-temperature shutdown
Automatic overload protection
Short-circuit protection
Model | 1000W-6000W |
DC Input | 1KW-3KW: DC12V & DC24V& DC48V(Select one) 4KW-6KW: DC24V & DC48V(Select one) |
AC ouput | AC220V & AC110V & AC100V & AC230V & AC240V (Select one) |
Nominal Output Frequency (Hz) | 50HZ & 60HZ(Automatic selection) |
UPS function | Yes (Can give up the use ) |
AC charging function | Yes (Can give up the use ) |
Utility Model Specifications |
| AC220V | AC110V |
Efficiency | ≥ 98% |
Input Wave Type | Pure sine wave (utility or generator) | Pure sine wave (utility or generator) |
Input Voltage Range | AC 154V~AC263V | AC 77V~132V |
Nominal Input Voltage | 220Vac/230Vac/240Vac | 110Vac/120Vac/130Vac |
Low Voltage shutoff | 154Vac± 4% | 77Vac± 4% |
Low Voltage Recovery | 164Vac ± 4% | 82Vac ± 4% |
Over voltage Shut off | 263Vac± 4% | 132Vac± 4% |
Over Voltage Recovery | 253Vac± 4% | 127Vac± 4% |
Nominal Input Frequency | 50Hz/ 60Hz (auto detect) | 50Hz/ 60Hz (auto detect) |
Output Wave Type | Same as the input wave type | Same as the input wave type |
Transfer Time (Ac to Dc) | < 10ms | < 10ms |
Transfer Time (Dc to Ac) | < 5ms | < 5ms |
Inverter Mode Specification |
Power Factor | 1 (Sufficient output power) |
Rated Output Voltage (V) | 220Vac/230Vac/240Vac | 110Vac/120Vac/130Vac |
Nominal Output Frequency (Hz) | 50/60 ± 0.3Hz (auto detect) |
Output Voltage Range | ± 10% rms |
Efficiency | > 88% (DC12V: > 88%, DC24V: > 90%, DC48V: > 94%) |
Over-Load Protection | (110%< load< 125%) ± 10%: Fault (shutdown output) after 15 minutes; |
(125%< load< 150%) ± 10%: Fault (shutdown output) after 10s; |
Load> 150% ± 10%: Fault (shutdown output) after 20s; |
Low Battery Alarm | 10.5Vdc ± 0.3Vdc (If 12V Input) |
21.0Vdc ± 0.6Vdc (If 24V Input) |
42.0Vdc ± 0.6Vdc (If 48V Input) |
Low DC input voltage automatic shut-down | 10.0Vdc ± 0.3Vdc(If 12V Input) |
20.0vdc± 0.6Vdc (If 24V Input) |
40.0vdc± 0.6Vdc (If 48V Input) |
High DC input voltage warning & outage | 16Vdc ± 0.3Vdc (If 12V Input) |
32Vdc ± 0.6Vdc (If 24V Input) |
64Vdc ± 0.6Vdc (If 48V Input) |
High DC input voltage Recover | 15.5Vdc ± 0.3Vdc(If 12V Input) |
31.0Vdc ± 0.6Vdc (If 24V Input) |
62.0Vdc ± 0.6Vdc (If 48V Input) |
Power-saving mode | < 10W |
Power on mode | 20W~60W |
Safety | CE, EMC, LVD, SGS, ISO9001 |
Communication port | RS232 |
Cooling | Cooling-Variable Speed Fan run under ventilation condition. |
Operating Temperature Range | 0° Cto 60° C |
Storage temperature | -15º C~60º C |
humidity | 5% to 95% |
Noise | Max 60dB |
Detailed parameters of electrified wire netting to battery charging |
Model | Specification | 1012 | 1024 | 2012 | 2024 | 3012 | 3024 | 3048 | 4024 | 4048 | 5024 | 5048 | 6024 | 6048 | Input voltage | 110Vac/120Vac/220Vac/230Vac | Input voltage range | 88~127Vac/165~255Vac | Output voltage | Depend on the batter type | Charge current | 35A | 20A | 65A | 35A | 75A | 45A | 30A | 35A | 35A | 35A | 40A | 75A | 50A | Charging the inverter for intelligent charging; , The size of the charge current is determined by the: The regulation of the inverter\Capacity of the battery at\battery voltage | Charge current correction | ± 5A | Initial Charge Voltage | Normal batteryvoltage 9.0 ~ 15.7V / 18.0 ~ 31.4V / 36.0 ~ 62.8V | Charger short-circuit protection | Circuit Breaker | Circuit breaker | 10A | 20A | 30A | 40A | Over voltage protection | When the battery voltage > 15.7Vdc/31.4Vdc/62.8Vdc, every second sounds 0.5 second, it breaks down after 60 seconds. | | model | Net weight (KG) | gross weight (KG) | product size (L*W*H)MM | package size (L*W*H)MM | | | 1KW | 12 | 13 | 358*188*168 | 480*330*285 | | | 1.5KW | 18 | 19.2 | 425*188*168 | 535*330*285 | | | 2KW | 19.5 | 20.9 | 425*188*168 | 535*330*285 | | | 3KW | 24 | 25.4 | 425*188*168 | 535*330*285 | | | 4KW | 36 | 37.5 | 622*188*168 | 730*330*285 | | | 5KW | 41 | 43 | 622*188*168 | 730*330*285 | | | 6KW | 44 | 46 | 622*188*168 | 730*330*285 | | | For reference only, if there is a change without notice | | | | | | | | | | | | | | | | | | | | | | If you want to purchase this product, Please make sure the following parameters. |
Power rating | | 1KW, 1.5KW, 2KW, 3KW, 4KW, 5KW, 6KW |
DC volts | | DC12V & DC24V & DC48V & DC36V |
AC volts | | AC110V & AC220V & AC100V & AC120V & AC230V & AC240V |
Frequency | | 50HZ & 60HZ |
The UPS function | | YES & NO |
The use of occasions | | Solar & Wind & Car & Family expenses & Industrial use & other |
AC priority use & DC priority use | | AC priority use & DC priority use |
If DC priority use | | There are two kinds of programming: 1, every time itstarts, After the batteris is full, and then converted to DC supply. 2, After the batteris is 13.5V/27V/54V, and then converted to DC supply. |
AC charging function | | YES & NO |
Trade Terms | | EXW, FOB, FCA, FAS, CIF, CFR, DEQ, and so on |
Other description | |
| | | | | | | |